{"id":20585,"date":"2023-05-26T10:40:38","date_gmt":"2023-05-26T15:40:38","guid":{"rendered":"https:\/\/www.polywater.com\/?p=20585"},"modified":"2025-05-14T13:33:12","modified_gmt":"2025-05-14T18:33:12","slug":"cable-compatibility-in-undergrounding","status":"publish","type":"post","link":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/","title":{"rendered":"Cable Compatibility in Undergrounding"},"content":{"rendered":"<div id=\"vyLightbox\"><\/div>\n<p>A key to underground installations is cable longevity. Improvements in cable design increase the lifespan of the installation. When cable is pulled into duct, two other important factors affecting cable longevity involve cable lubricants. <a href=\"https:\/\/www.polywater.com\/en\/products\/lubricants\/?industry=lubricants\" target=\"_blank\" rel=\"noopener\">Lubricants<\/a> reduce friction as the heavy, stiff wires or cables are pulled long distances into buried conduit. Because these cable systems are expensive, and because 90% of cable damage reportedly occurs during installation\u2014typically due to the use of an insufficient quantity or inadequate quality of lubricant\u2014a specialty, <a href=\"https:\/\/www.polywater.com\/en\/product\/polywater-nn-lubricant\/\" target=\"_blank\" rel=\"noopener\">high-performance lubricant<\/a> is required.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-3619\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2020\/12\/Lube-Calc-page-pump-1.jpg\" alt=\"Polywater LZ Lubricant being pumped into a duct\" width=\"1000\" height=\"667\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2020\/12\/Lube-Calc-page-pump-1.jpg 1000w, https:\/\/www.polywater.com\/wp-content\/uploads\/2020\/12\/Lube-Calc-page-pump-1-300x200.jpg 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2020\/12\/Lube-Calc-page-pump-1-768x512.jpg 768w\" sizes=\"auto, (max-width: 1000px) 100vw, 1000px\" \/><\/p>\n<p>But in conduit there is a secondary concern. After the cable is successfully pulled, the lubricant or its dried residue remains in contact with the cable sheath for decades. Thus, compatibility between the cable and the lubricant is essential. Incompatible lubricants damage cable jackets and can shorten their life expectancy by years, even decades in extreme cases. This is a fundamentally important consideration in undergrounding, the whole point of which is to ensure system resiliency and longevity. Engineers and designers cannot allow one of the least expensive components in the installation\u2014the lubricant\u2014to threaten the entire economic rationalization of the project.<\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/coefficient-of-friction-in-cable-pulling-part-1\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Coefficient of Friction in Cable Pulling &#8212; Part 1<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Wait \u2026 What?<\/h2>\n<p>Many engineers expect that this is a problem solved long ago. However, neither the cable jacket nor cable lubricant industries are static. Jacket design is ever-evolving, and new lubricant formulations are continually introduced. Cable jackets vary by manufacturer, even within a general category (e.g., polyethylene). Cable lubricant manufacturers have unique, often proprietary formulations based on completely different chemistries. It is the rule rather than the exception that a given lubricant is suitable for one type of cable, but less so for another.<\/p>\n<p>What\u2019s to be done? Don\u2019t all manufacturers\u2014of cables and lubricants alike\u2014regularly test for compatibility? The truth is, some more than others. In all things, it is buyer beware.<\/p>\n<h2>Due Diligence<\/h2>\n<p>Preventing a pulling compound from ruining your cable is a two-step process. One: Work with reputable cable and lubricant manufacturers to ensure materials are compatible. Two: Specify a compatible lubricant to prevent the choice from being left up to installers who may have no inkling of the issue.<\/p>\n<h2>How is Compatibility Tested?<\/h2>\n<p>Various methods have been used to test the compatibility of cable lubricants with jacket materials. Typically, the wire or cable jacket material is aged in the lubricant and the physical properties (tensile and elongation) are compared to a control. For polyethylene cable, a version of the Environmental Stress Crack Resistance (ESCR) test may be run. For electrical cables, dielectric breakdown or volume resistivity may also be tested after aging.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20698\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png\" alt=\"A scientist observes a test of the elongation of a conduit sample. The plastic strip is pulled from both ends by two gripping clamps.\" width=\"800\" height=\"340\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample-300x128.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample-768x326.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<h2>A Standard is Created<\/h2>\n<p>In 1996, Polywater\u00ae was instrumental in the development of the IEEE 1210 &#8220;Standard Tests for Determining Compatibility of Cable Lubricants with Wire and Cable.&#8221; It was created at the request of both cable manufacturers and end-users. At that time, increasing cable performance expectations coupled with the longevity of cable in conduit systems put a spotlight on the important role cable sheaths and coverings play in cable protection.<\/p>\n<p>Potential interaction of lubricants with cable was a major concern, and for good reason. History showed that:<\/p>\n<ul>\n<li style=\"list-style-type: none;\">\n<ul>\n<li>Certain wax emulsion lubricants negatively affect semi-conducting jackets.<\/li>\n<li>Some soaps and waxes can &#8220;stress crack&#8221; polyethylene jackets.<\/li>\n<li>Petroleum greases and oils wreak havoc with many cable jacket materials.<\/li>\n<\/ul>\n<\/li>\n<\/ul>\n<p>IEEE 1210 provides a basis for evaluation of a specific lubricant&#8217;s compatibility with a specific cable jacket. The second revision of this standard was approved in 2023. This revision update was developed in cooperation with Canadian Standards Association (CSA). To better understand the 1210 standard, consider the physical test procedures and what they show about compatibility.<\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/hawaiian-electrical-company-heco-and-the-pearl-harbor-cable-pull\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Hawaiian Electrical Company (HECO) and the Pearl Harbor Cable Pull<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Physical Testing<\/h2>\n<p>The primary function of medium and high-voltage cable jackets is physical protection. Jacket physical properties (tensile and elongation) are a primary focus in 1210. In this testing, there is a 30-day aging test compared to a water-aged control and a shorter, high-temperature test compared to a water-aged control and a non-aged control. The high-temperature test condition is jacket-specific and based on NEMA\/ICEA time and temperature requirements for aging of the jacket material and polymer group.<\/p>\n<p>Polywater lubricants are all extensively tested to this standard. Below are results from this testing on LLDPE, a common cable jacket material. Note that the NEMA\/ICEA aging test for polyethylene (PE) jackets is 2 days at 100\u00b0C, and the test is modified to include lubricant immersion of the aged sample. Percent retention requirements are listed in the chart below.<\/p>\n<p>Each test specimen yields a tensile and elongation result. These values are averaged over three tests and compared to a control as noted. Results here are presented as a comparison to a control. A full test report includes the tensile force at break as well as the percent elongation. Values for each of the trials are typically shared.<\/p>\n<p><strong>Table 1: Different Lubricants with LLDPE Cable Jacket<\/strong><\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20690\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Table-1.png\" alt=\"Table 1-Different Lubricants with LLDPE Cable Jacket\" width=\"815\" height=\"296\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Table-1.png 815w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Table-1-300x109.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Table-1-768x279.png 768w\" sizes=\"auto, (max-width: 815px) 100vw, 815px\" \/><\/p>\n<p>Data can also be visualized as a bar graph:<\/p>\n<p><strong>Graph 1: LLDPE Cable Jacket with Various Lubricants Comparing Tensile Values to Control<\/strong><br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20650\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-1-LLDPE-with-Various-Lubricants-Tensile-Values-Compared-to-Control.png\" alt=\"Graph 1-LLDPE with Various Lubricants Tensile Values Compared to Control\" width=\"800\" height=\"393\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-1-LLDPE-with-Various-Lubricants-Tensile-Values-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-1-LLDPE-with-Various-Lubricants-Tensile-Values-Compared-to-Control-300x147.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-1-LLDPE-with-Various-Lubricants-Tensile-Values-Compared-to-Control-768x377.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p><strong>Graph 2: LLDPE Cable Jacket with Various Lubricants Comparing Elongation Values to Control<\/strong><br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20654\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-2-LLDPE-with-Various-Lubricants-Elongation-Values-Compared-to-Control.png\" alt=\"Graph 2-LLDPE with Various Lubricants Elongation Values Compared to Control\" width=\"800\" height=\"400\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-2-LLDPE-with-Various-Lubricants-Elongation-Values-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-2-LLDPE-with-Various-Lubricants-Elongation-Values-Compared-to-Control-300x150.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-2-LLDPE-with-Various-Lubricants-Elongation-Values-Compared-to-Control-768x384.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p>Polywater lubricants show good compatibility with LLDPE. Each lubricant must be individually tested, as results will differ depending on the chemistry of the lubricant.<\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/solution-story\/the-lubricant-difference-matching-product-to-project\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Solution Story: The Lubricant Difference: Matching Product to Project<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Different Jackets<\/h2>\n<p>As might be expected, the same lubricant will act differently on different jackets. Below, the results from testing one lubricant with different cable jacket types are graphed.<\/p>\n<p><strong>Graph 3: Various Cable Jacket Compounds Aged in Lubricant \u2013 Tensile Strength Compared to Control<\/strong><br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20658\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-3-Cable-Jacket-Compounds-Aged-in-Lubricant-Tensile-Strength-Compared-to-Control.png\" alt=\"Graph 3-Cable Jacket Compounds Aged in Lubricant Tensile Strength Compared to Control\" width=\"800\" height=\"393\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-3-Cable-Jacket-Compounds-Aged-in-Lubricant-Tensile-Strength-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-3-Cable-Jacket-Compounds-Aged-in-Lubricant-Tensile-Strength-Compared-to-Control-300x147.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-3-Cable-Jacket-Compounds-Aged-in-Lubricant-Tensile-Strength-Compared-to-Control-768x377.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p><strong>Graph 4: Cable Jacket Compounds Aged in Lubricant \u2013 Elongation Percent Compared to Control<\/strong><br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20662\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-4-Cable-Jacket-Compounds-Aged-in-Lubricant-Elongation-Percent-Compared-to-Control.png\" alt=\"Graph 4-Cable Jacket Compounds Aged in Lubricant Elongation Percent Compared to Control\" width=\"800\" height=\"395\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-4-Cable-Jacket-Compounds-Aged-in-Lubricant-Elongation-Percent-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-4-Cable-Jacket-Compounds-Aged-in-Lubricant-Elongation-Percent-Compared-to-Control-300x148.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-4-Cable-Jacket-Compounds-Aged-in-Lubricant-Elongation-Percent-Compared-to-Control-768x379.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p>This lubricant shows good compatibility with most cable jacket types. However, there is some incompatibility with CSPE blend tested at higher temperatures. This cable lubricant would not be suitable for use with cables utilizing this CSPE covering.<\/p>\n<h2>Jacket Failure<\/h2>\n<p>Incompatibility between lubricant and cable jacket is usually seen as loss of tensile strength or elongation in the material. This is often visually apparent as pitting or other surface damage. Sometimes represented by a softening or even excess flexibility. On rare occasions, lubricant can completely disintegrate jacket materials.<\/p>\n<p>As shown in Photo 1, the low smoke, polyolefin LSZH (Low Smoke Zero Halogen) blend was aged in a wax-based lubricant and softened to the point that it fell apart even before testing.<\/p>\n<p><strong>Photo 1<\/strong><br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20682\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Photo-1-400p.png\" alt=\"The shards of a shattered plastic conduit strewn about a paper towel\" width=\"400\" height=\"294\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Photo-1-400p.png 400w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Photo-1-400p-300x221.png 300w\" sizes=\"auto, (max-width: 400px) 100vw, 400px\" \/><\/p>\n<p>As shown in Photo 2, a different low smoke, polyolefin blend, appears to literally melt when a grease is used for cable installation.<\/p>\n<p><strong>Photo 2<br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-21360\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/05\/Photo-2-400p.png\" alt=\"The shards of a shattered plastic conduit strewn about a black countertop.\" width=\"400\" height=\"238\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/05\/Photo-2-400p.png 400w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/05\/Photo-2-400p-300x179.png 300w\" sizes=\"auto, (max-width: 400px) 100vw, 400px\" \/><\/strong><\/p>\n<p>Wax and petroleum-based cable lubricants are not suitable for this jacket type. While these lubricants may be effective at lowering friction, they should not be used. Always consider compatibility when making a cable lubricant choice.<\/p>\n<h2>Cable Jacket Polymers<\/h2>\n<p>Within each polymer type or group (such as LLDPE or PVC) there are many individual blends. The polymer blend developed for each cable jacket is chosen for both performance and processing. Performance considerations include tensile strength, impact and puncture resistance, flexibility, and fire resistance. Processing characteristics may include ease of extrusion, melt flow, and shearing characteristics. Many cable manufacturers utilize multiple blends depending on cable style based on end use and performance expectations. The bottom line is that each cable sheath is unique. For some material groups, extensive testing may be required.<\/p>\n<p>We obtained dozens of LSZH polyolefin blends for a lubricant compatibility study. Because low smoke jackets have shown incompatibility with some water-based wire and cable lubricants, Polywater has tested this polymer group extensively.<\/p>\n<p>Data in the following graphs 5-8 show that each blend of LSZH polyolefin is unique. Two different lubricants tested with these blends show dramatically different results.<\/p>\n<p><strong>Graph 5: 10 Blends LSZH Aged in Lubricant A Tensile and Elongation Aged at 50\u00b0C, Compared to Control<\/strong><\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20666\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-5-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-50c-Compared-to-Control.png\" alt=\"Graph 5-10 Blends LSZH Aged in Lubricant A Tensile and Elongation Aged at 50c Compared to Control\" width=\"800\" height=\"348\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-5-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-50c-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-5-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-50c-Compared-to-Control-300x131.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-5-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-50c-Compared-to-Control-768x334.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p>At 100\u00b0C, cable jacket material is exposed to boiling water or\u2013in the case of water-based lubricants\u2013boiling lubricant. If there is incompatibility between the jacket and lubricant, it can usually be discovered in high-temperature testing.<\/p>\n<p><strong>Graph 6: 10 Blends LSZH Aged in Lubricant A Tensile and Elongation Aged at 100\u00b0C, Compared to Control<\/strong><\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20670\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-6-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-100c-Compared-to-Control.png\" alt=\"Graph 6-10 Blends LSZH Aged in Lubricant A Tensile and Elongation Aged at 100c Compared to Control\" width=\"800\" height=\"368\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-6-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-100c-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-6-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-100c-Compared-to-Control-300x138.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-6-10-Blends-LSZH-Aged-in-Lubricant-A-Tensile-and-Elongation-Aged-at-100c-Compared-to-Control-768x353.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p>For Lubricant A, some blends of the LSZH material are compatible and others are not.<\/p>\n<p>Test results for Lubricant B are shown below. Here the test results show good consistency from one polymer blend to the next.<\/p>\n<p><strong>Graph 7: 11 Blends LSZH Aged in Lubricant B Tensile and Elongation Aged at 50\u00b0C, Compared to Control<\/strong><\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20674\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-7-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-50C-Compared-to-Control.png\" alt=\"Graph 7-11 Blends LSZH Aged in Lubricant B Tensile and Elongation Aged at 50C Compared to Control\" width=\"800\" height=\"325\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-7-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-50C-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-7-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-50C-Compared-to-Control-300x122.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-7-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-50C-Compared-to-Control-768x312.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p><strong>Graph 8: 11 Blends LSZH Aged in Lubricant B Tensile and Elongation Aged at 100\u00b0C, Compared to Control<\/strong><\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-20678\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-8-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-100C-Compared-to-Control.png\" alt=\"Graph 8-11 Blends LSZH Aged in Lubricant B Tensile and Elongation Aged at 100C Compared to Control\" width=\"800\" height=\"373\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-8-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-100C-Compared-to-Control.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-8-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-100C-Compared-to-Control-300x140.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/Graph-8-11-Blends-LSZH-Aged-in-Lubricant-B-Tensile-and-Elongation-Aged-at-100C-Compared-to-Control-768x358.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/p>\n<p>Even at high-temperature testing, Lubricant B is compatible with all the jackets tested. This is not a surprise. Lubricant B is <a href=\"https:\/\/www.polywater.com\/en\/product\/polywater-lz-lubricant\/\" target=\"_blank\" rel=\"noopener\">Polywater LZ<\/a> and was specially developed for compatibility and performance on LSZH jacket material.<\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/total-cost-of-ownership-tools-for-your-future\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Total Cost of Ownership: Tools for Your Future<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Conclusion<\/h2>\n<p>The utility of IEEE 1210 and testing for compatibility in general is obvious. The standard provides a way to evaluate any lubricant\u2019s interaction with a cable jacket. However, engineers should be wary of blanket statements. A simple, stand-alone claim that a lubricant has been tested and passed IEEE 1210 is essentially meaningless. It is only meaningful if it passed a test with the specific cable to be used. There is no universal 1210 test. Every test must be specific to lubricant and cable.<\/p>\n<h2>Other Considerations<\/h2>\n<p>IEEE 1210 does not ensure lubricant performance. Water passes the 1210 but is not a good pulling lubricant. While compatibility is critical, it&#8217;s equally important that a lubricant is functional and efficient. A few key properties in a high-performance, specification-grade pulling lubricant include:<\/p>\n<ul>\n<li style=\"list-style-type: none;\">\n<ul>\n<li><strong>Coefficient of Friction<\/strong> \u2014 (How slippery is the lubricant? Always specific to jacket type and conduit type.)<\/li>\n<li><strong>Coefficient of Friction &#8220;Dry&#8221;<\/strong> \u2014 (Is the lubricant effective for long pulls? Can cable be later adjusted?)<\/li>\n<li><strong>Amount and Nature of Residue<\/strong> \u2014 (Does residue &#8220;glue&#8221; in cable over time or block conduits?)<\/li>\n<li><strong>Residue Combustibility<\/strong> \u2014 (Does lube residue affect flame propagation character of fire-retardant cables?)<\/li>\n<li><strong>Coating and Cling Character in Application<\/strong> \u2014 (Will lubricant coat the jacket? Does it stay on for long pulls?)<\/li>\n<li><strong>Chemical Stability<\/strong> \u2014 (What are the effects of cold and\/or warm storage?)<\/li>\n<li><strong>Environmental<\/strong> \u2014 (Is the lubricant toxic, a hazardous waste, etc.?)<\/li>\n<\/ul>\n<\/li>\n<\/ul>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/products\/lubricants\/?industry=lubricants\" target=\"_blank\" rel=\"noopener\"><strong>Find the Industrial Lubricant for Your Needs<\/strong><\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Summary<\/h2>\n<p>The chemistry of lubricants and cable jackets is diverse and ever changing. This provides the potential for adverse chemical interactions that can damage cable and defeat the purpose of undergrounding utility infrastructure for system resiliency. For confidence that cable longevity is maximized, engineers should work with lubricant manufacturers who routinely test for compatibility, work closely with cable manufacturers on new product introductions, and can provide results on demand for the specific cables and lubricants you use.<\/p>\n<p>Over the years, Polywater has performed hundreds of IEEE 1210 compatibility tests on untold combinations of lubricant and cable. We utilize the tests to develop new lubricant products, assist cable manufacturers in their development of new cable jackets, and to support end users in their due diligence and specification of compatible cable lubricants.<\/p>\n<h2>Have any questions?<\/h2>\n<p><button class=\"button button--primary\" data-micromodal-trigger=\"polywater-modal--email-us-form\">Email Us <\/button><\/p>\n<div class=\"modal micromodal-slide\" id=\"polywater-modal--email-us-form\" aria-hidden=\"true\"><div class=\"modal__overlay\" tabindex=\"-1\" data-micromodal-close><div class=\"modal__container\" role=\"dialog\" aria-modal=\"true\" aria-labelledby=\"polywater-modal--email-us-form-title\"><header class=\"modal__header\"><h2 id=\"polywater-modal--email-us-form-title\">Email Us Form<\/h2><button class=\"button--secondary modal__close\" aria-label=\"Close modal\" data-micromodal-close><\/button><\/header><div id=\"polywater-modal--email-us-form-content\"><!-- [if lte IE 8]>\r\n<script charset=\"utf-8\" type=\"text\/javascript\" src=\"\/\/js.hsforms.net\/forms\/v2-legacy.js\"><\/script>\r\n<![endif]-->\r\n<script charset=\"utf-8\" type=\"text\/javascript\" src=\"\/\/js.hsforms.net\/forms\/v2.js\"><\/script>\r\n<script>\r\nhbspt.forms.create({\r\n  region: \"na1\",\r\n  portalId: \"6060295\",\r\n  formId: \"7658eeb9-0cf9-469d-a7f1-0f033127bb9d\",\r\n  onFormReady: function (a) {\r\n    a.on('change', function(){\r\n      var zip = a.find('input[name=\"zip\"]');\r\n      if( zip ) {\r\n        if( zip.val() && zip.val().length > 4 ) {\r\n          var url = \"https:\/\/api.zippopotam.us\/us\/\" + zip.val();\r\n          var client = new XMLHttpRequest();\r\n          client.open(\"GET\", url, true);\r\n          client.onreadystatechange = function() {\r\n            if(client.readyState == 4) {\r\n              var resp = JSON.parse(client.responseText);\r\n              var city = resp.places[0]['place name'];\r\n              var state = resp.places[0]['state'];\r\n              a.find('input[name=\"city\"]').val(city);\r\n              a.find('input[name=\"state\"]').val(state);\r\n            };\r\n          };\r\n          client.send();\r\n        }\r\n      }\r\n    });\r\n  },\r\n});\r\n<\/script><\/div><\/div><\/div><\/div>","protected":false},"excerpt":{"rendered":"<p>A key to underground installations is cable longevity. Improvements in cable design increase the lifespan of the installation. When cable&#8230;<\/p>\n","protected":false},"author":7,"featured_media":20698,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_relevanssi_hide_post":"","_relevanssi_hide_content":"","_relevanssi_pin_for_all":"","_relevanssi_pin_keywords":"","_relevanssi_unpin_keywords":"","_relevanssi_related_keywords":"","_relevanssi_related_include_ids":"","_relevanssi_related_exclude_ids":"","_relevanssi_related_no_append":"","_relevanssi_related_not_related":"","_relevanssi_related_posts":"","_relevanssi_noindex_reason":"","footnotes":""},"categories":[2992,2982,2984,2997,2998,3004,3010],"tags":[],"industry-type":[2980,2981],"writer":[2712],"class_list":["post-20585","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-underground-cabling","category-cable-in-duct-installation","category-cable-pulling","category-system-hardening","category-asset-protection","category-content-type","category-technical-paper","industry-type-telecommunications","industry-type-electrical-infrastructure","writer-chris-jonnes"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.7 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Cable Compatibility in Undergrounding - Polywater<\/title>\n<meta name=\"description\" content=\"Cable systems are expensive. 90% of cable damage reportedly occurs during installation typically due to an insufficient quantity or inadequate quality of lubricant.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Cable Compatibility in Undergrounding - Polywater\" \/>\n<meta property=\"og:description\" content=\"Cable systems are expensive. 90% of cable damage reportedly occurs during installation typically due to an insufficient quantity or inadequate quality of lubricant.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/\" \/>\n<meta property=\"og:site_name\" content=\"Polywater\" \/>\n<meta property=\"article:published_time\" content=\"2023-05-26T15:40:38+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2025-05-14T18:33:12+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png\" \/>\n\t<meta property=\"og:image:width\" content=\"800\" \/>\n\t<meta property=\"og:image:height\" content=\"340\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"Rick Schmolke\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Rick Schmolke\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"11 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/\"},\"author\":{\"name\":\"Rick Schmolke\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#\\\/schema\\\/person\\\/a60fe81e63d35625d9be04310f1601f4\"},\"headline\":\"Cable Compatibility in Undergrounding\",\"datePublished\":\"2023-05-26T15:40:38+00:00\",\"dateModified\":\"2025-05-14T18:33:12+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/\"},\"wordCount\":1824,\"image\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png\",\"articleSection\":[\"Underground Cabling\",\"Cable-in-duct Installation\",\"Cable Pulling\",\"System Hardening\",\"Asset Protection\",\"Content Type\",\"Technical Paper\"],\"inLanguage\":\"en-US\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/\",\"url\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/\",\"name\":\"Cable Compatibility in Undergrounding - Polywater\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png\",\"datePublished\":\"2023-05-26T15:40:38+00:00\",\"dateModified\":\"2025-05-14T18:33:12+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#\\\/schema\\\/person\\\/a60fe81e63d35625d9be04310f1601f4\"},\"description\":\"Cable systems are expensive. 90% of cable damage reportedly occurs during installation typically due to an insufficient quantity or inadequate quality of lubricant.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png\",\"contentUrl\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2023\\\/04\\\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png\",\"width\":800,\"height\":340,\"caption\":\"A scientist observes a test of the elongation of a conduit sample. The plastic strip is pulled from both ends by two gripping clamps.\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/cable-compatibility-in-undergrounding\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Cable Compatibility in Undergrounding\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#website\",\"url\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/\",\"name\":\"Polywater\",\"description\":\"Solutions at work.\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#\\\/schema\\\/person\\\/a60fe81e63d35625d9be04310f1601f4\",\"name\":\"Rick Schmolke\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g\",\"caption\":\"Rick Schmolke\"},\"url\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/author\\\/rick\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Cable Compatibility in Undergrounding - Polywater","description":"Cable systems are expensive. 90% of cable damage reportedly occurs during installation typically due to an insufficient quantity or inadequate quality of lubricant.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/","og_locale":"en_US","og_type":"article","og_title":"Cable Compatibility in Undergrounding - Polywater","og_description":"Cable systems are expensive. 90% of cable damage reportedly occurs during installation typically due to an insufficient quantity or inadequate quality of lubricant.","og_url":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/","og_site_name":"Polywater","article_published_time":"2023-05-26T15:40:38+00:00","article_modified_time":"2025-05-14T18:33:12+00:00","og_image":[{"width":800,"height":340,"url":"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png","type":"image\/png"}],"author":"Rick Schmolke","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Rick Schmolke","Est. reading time":"11 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#article","isPartOf":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/"},"author":{"name":"Rick Schmolke","@id":"https:\/\/www.polywater.com\/en\/#\/schema\/person\/a60fe81e63d35625d9be04310f1601f4"},"headline":"Cable Compatibility in Undergrounding","datePublished":"2023-05-26T15:40:38+00:00","dateModified":"2025-05-14T18:33:12+00:00","mainEntityOfPage":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/"},"wordCount":1824,"image":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#primaryimage"},"thumbnailUrl":"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png","articleSection":["Underground Cabling","Cable-in-duct Installation","Cable Pulling","System Hardening","Asset Protection","Content Type","Technical Paper"],"inLanguage":"en-US"},{"@type":"WebPage","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/","url":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/","name":"Cable Compatibility in Undergrounding - Polywater","isPartOf":{"@id":"https:\/\/www.polywater.com\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#primaryimage"},"image":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#primaryimage"},"thumbnailUrl":"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png","datePublished":"2023-05-26T15:40:38+00:00","dateModified":"2025-05-14T18:33:12+00:00","author":{"@id":"https:\/\/www.polywater.com\/en\/#\/schema\/person\/a60fe81e63d35625d9be04310f1601f4"},"description":"Cable systems are expensive. 90% of cable damage reportedly occurs during installation typically due to an insufficient quantity or inadequate quality of lubricant.","breadcrumb":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#primaryimage","url":"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png","contentUrl":"https:\/\/www.polywater.com\/wp-content\/uploads\/2023\/04\/A-scientist-observes-a-test-of-the-elongation-of-a-conduit-sample.png","width":800,"height":340,"caption":"A scientist observes a test of the elongation of a conduit sample. The plastic strip is pulled from both ends by two gripping clamps."},{"@type":"BreadcrumbList","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/cable-compatibility-in-undergrounding\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.polywater.com\/en\/"},{"@type":"ListItem","position":2,"name":"Cable Compatibility in Undergrounding"}]},{"@type":"WebSite","@id":"https:\/\/www.polywater.com\/en\/#website","url":"https:\/\/www.polywater.com\/en\/","name":"Polywater","description":"Solutions at work.","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.polywater.com\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/www.polywater.com\/en\/#\/schema\/person\/a60fe81e63d35625d9be04310f1601f4","name":"Rick Schmolke","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g","caption":"Rick Schmolke"},"url":"https:\/\/www.polywater.com\/en\/knowledge-hub\/author\/rick\/"}]}},"_links":{"self":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/posts\/20585","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/users\/7"}],"replies":[{"embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/comments?post=20585"}],"version-history":[{"count":0,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/posts\/20585\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/media\/20698"}],"wp:attachment":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/media?parent=20585"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/categories?post=20585"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/tags?post=20585"},{"taxonomy":"industry-type","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/industry-type?post=20585"},{"taxonomy":"writer","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/writer?post=20585"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}