{"id":17181,"date":"2022-08-26T19:12:16","date_gmt":"2022-08-27T00:12:16","guid":{"rendered":"https:\/\/www.polywater.com\/?p=17181"},"modified":"2025-05-20T12:24:08","modified_gmt":"2025-05-20T17:24:08","slug":"is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance","status":"publish","type":"post","link":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/","title":{"rendered":"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance."},"content":{"rendered":"<div id=\"vyLightbox\"><\/div>\n<h2>What the Codes Say:<\/h2>\n<p>The infographic linked <a href=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/System-Hardening-Paper-Infographic-V2-2.pdf\" target=\"_blank\" rel=\"noopener\">here<\/a> and also found below, illustrates the need for duct seals and lists various governing standards. Let\u2019s review the language in a sampling of pertinent electrical and communication industry codes from around the world:<\/p>\n<h3>NEC 225.27 Raceway Seal:<\/h3>\n<p><em>\u00a0 \u201cWhere a raceway enters a building or structure from outside, it shall be sealed. Spare or unused raceways shall also be sealed. Sealants shall be identified for use with cable insulation, conductor insulation, bare conductor, shield, or other components.\u201d<\/em><\/p>\n<h3>NEC 230.8 Raceway Seal:<\/h3>\n<p><em>\u00a0 \u201cWhere a service raceway enters a building or structure from an underground distribution system, it shall be sealed in accordance with 300.5(G). Spare or unused raceways shall also be sealed. Sealants shall be identified for use with the cable insulation, shield, or other components.\u201d<\/em><\/p>\n<h3>NEC 300.5 (D)) G) Raceway Seals:<\/h3>\n<p><em>\u00a0 \u201cConduits or raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends. Spare or unused raceways shall also be sealed. Sealants shall be identified for use with cable insulation, conductor insulation, bare conductor, shield, or other components.\u201d<\/em><\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/sealing-conduits-for-resilient-electrical-and-telecommunication-systems\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Sealing Conduits for Resilient Electrical and Telecommunication Systems<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>NEC 300.7 (A) Sealing:<\/h3>\n<p><em>\u00a0 \u201cWhere portions of a raceway or sleeve are known to be subjected to different temperatures, and where condensation is known to be a problem, as in cold storage areas of buildings or where passing from the interior to the exterior of a building, the raceway or sleeve shall be filled with an approved material to prevent the circulation of warm air to a colder section of the raceway or sleeve. An explosion proof seal shall not be required for this purpose.\u201d<\/em><br \/>\n<a href=\"https:\/\/www.polywater.com\/en\/resource\/achieving-resiliency-by-sealing-vulnerabilities\/\" target=\"_blank\" rel=\"noopener\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-12530 size-full alignright\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/System-Resiliency-Infographic-thumbnail-w-button-300p.jpg\" width=\"225\" height=\"290\" \/><\/a><\/p>\n<h3>NEC 300.50 (F) Raceway Seal:<\/h3>\n<p><em>\u00a0 \u201cWhere a raceway enters from an underground system, the end within the building shall be sealed with an identified compound so as to prevent the entrance of moisture or gases, or it shall be so arranged to prevent moisture from contacting live parts.\u201d<\/em><\/p>\n<h3>NEC 501.15 (B)(2) Conduit Seals, Class 1 Division 2:<\/h3>\n<p><em>\u00a0 \u201cA conduit seal shall be required in each conduit run leaving a Class 1, Division 2 location&#8230; and it shall be designed and installed to minimize the amount of gas or vapor within the portion of the conduit installed in the Division 2 location&#8230; Such seals shall not be required to be explosion proof&#8230;\u201d<\/em><\/p>\n<h3>NESC 322 (b)(4):<\/h3>\n<p><em>\u00a0 \u201cThe portion of a conduit installed through an exterior building wall, floor, or roof shall have seals inside the conduit and external seals on the outside surface of the conduit at the point of entry to the building intended to limit the likelihood of the entrance of gas into the building. The use of seals may be supplemented by gas-venting devices in order to minimize building up of positive gas pressures in the conduit.\u201d<\/em><\/p>\n<h3>ITU Rec. ITU-T L.92:<\/h3>\n<p><em>\u00a0 \u201c&#8230; sealing the ends of the plastic tubes (at the manholes\/pits of our underground infrastructure) with foam filler. Outside plant facilities are also damaged by floods. Water can enter manholes, hand-holes and cable tunnels, which can cause telecommunication equipment to break down. Therefore, manholes and hand-holes are required to be water tight. Cables entering or exiting a manhole or hand-hole have to be sealed.\u201d<\/em><\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/duct-seals-prevent-ruinous-water-damage\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Duct Seals Prevent Ruinous Water Damage<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>ITU Rec. ITU-T L.162:<\/h3>\n<p><em>\u00a0 \u201cIt is mandatory to use pipe \u2013 microduct sealing elements (sealing between pipe and microducts), in order to ensure \u2026 the seal against the entry of liquids and gases \u2026 to protect the branch of microducts. Microcable should be sealed to the microduct both in the cable chamber adjacent to the building as well as inside the building. The installation of empty (spare) microducts that do not contain microcables, should also be sealed in the cable chamber, inside the building.\u201d<\/em><\/p>\n<h3>TIA-758-B Standard 5.1.1.2.8:<\/h3>\n<p><em>\u00a0 \u201cDucts shall be sealed to resist liquid and gas infiltration at all maintenance holes and building entrance point locations.\u201d<\/em><\/p>\n<h3>TIA-758-B Standard 5.4.2.3:<\/h3>\n<p><em>\u00a0 \u201cAll conduits shall be plugged to restrict infiltration of gas, water, and vermin.\u201d<\/em><\/p>\n<h3>BICSI-TDMM:<\/h3>\n<p><em>\u00a0 \u201cSeal all underground conduits to prevent gases and water from entering the building or other MHs via the ductbank.\u201d<\/em><\/p>\n<h3>DIN 18322:2019-09 3.7.2:<\/h3>\n<p><em>\u00a0 \u201cCable and conduit entries shall be tightly sealed so as to be watertight and gastight.\u201d<\/em><\/p>\n<h3>DIN 18322:2019-09 4.2.6:<\/h3>\n<p><em>\u00a0 \u201cSealing of conduits after cables, etc. have been laid.\u201d<\/em><\/p>\n<h3>CEC Rule J18-108:<\/h3>\n<p><em>\u00a0 \u201c\u2026 requires that conduit seals be installed in conduit systems where \u2026\u201d<\/em><\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.youtube.com\/watch?v=vePZ1po3m64\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>&#8220;Let&#8217;s Talk Cabling&#8221; Video Podcast: Best Way to Seal OSP Conduit<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>What the Codes Don\u2019t Say<\/h2>\n<p>The codes are essentially <em>material<\/em> specs; they require that ducts are sealed with some material. But they aren\u2019t specific as to what that material must be. Only one calls for the use of \u201cfoam filler\u201d. But it doesn\u2019t describe which of the nearly infinite number of foam variations should be used (e.g., open-cell, closed-cell, urethane-based, epoxy-based, etc.). The others generally leave the material choice to discretion. That allows not only for the use of any type of foam, but also other chemicals, such as duct putty. It also allows for the use of non-chemical materials such as mechanical seals. Even a wad of old rags may be interpreted as compliant. Sometimes the choices come with costly consequences.<\/p>\n<h3><img loading=\"lazy\" decoding=\"async\" class=\"alignnone size-full wp-image-17190\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/Banner-image-800p.png\" alt=\"A worker seals a duct in an electrical vault\" width=\"800\" height=\"450\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/Banner-image-800p.png 800w, https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/Banner-image-800p-300x169.png 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/Banner-image-800p-768x432.png 768w\" sizes=\"auto, (max-width: 800px) 100vw, 800px\" \/><\/h3>\n<h2>Material Spec vs. Performance Spec<\/h2>\n<p>Few of the codes, particularly those relating to non-mechanical seals for water or gas, are considered <em>performance<\/em> specs.\u202fOther than a few requiring that the sealant <em>\u201cbe identified for use with\u201d<\/em> ducts and cables\u2014in other words, compatible\u2014they list no specific test or performance criteria to meet. They establish no quantitative thresholds or time limits to which a seal must perform. For example, they don\u2019t state what level of water head pressure must be resisted, or how much gas pressure in psi a seal must hold. There are no ASTM, IEEE, UL, CSA, or other common testing regimes to follow.<\/p>\n<h2>What Could Go Wrong?<\/h2>\n<p>Problems can arise when installers use cheap, readily available sealing products that ostensibly meet a governing standard, but in practice don\u2019t produce effective or long-lasting seals appropriate for the circumstance. Most common is the use of duct putty or one-part aerosol \u201cgap and crack\u201d foams from DIY stores. Duct putty sags over time, rendering it unsuitable as a long-term solution. Open-cell foams are versatile but not appreciably watertight or airtight. A seal that passes inspection only to fail shortly thereafter\u2014or later when the crisis is at hand\u2014isn\u2019t really a seal. Costs related to seal failure often don\u2019t end with the cables, electrical apparatus, and telecommunications equipment damaged; they extend as well to the resulting service outages.<\/p>\n<table style=\"width: 100%; border: 3px solid #273A80; background-color: #69c3e8; margin: 15px 0px 15px 0px;\">\n<tbody>\n<tr>\n<td style=\"padding: 20px; text-align: center;\"><a href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/understanding-and-mitigating-manhole-explosions-an-interview-with-stuart-hanebuth\/\" target=\"_blank\" rel=\"noopener\"><strong>Related Content: <\/strong>Understanding and Mitigating Manhole Explosions: An Interview with Stuart Hanebuth<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>What Is the Solution?<\/h2>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"alignright wp-image-17186 size-medium\" src=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/AFT-seal-800p-300x169.jpg\" alt=\"Polywater AFT sealing a fiber optic duct\" width=\"300\" height=\"169\" srcset=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/AFT-seal-800p-300x169.jpg 300w, https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/AFT-seal-800p-768x432.jpg 768w, https:\/\/www.polywater.com\/wp-content\/uploads\/2022\/07\/AFT-seal-800p.jpg 800w\" sizes=\"auto, (max-width: 300px) 100vw, 300px\" \/>The codes are crucial in their requirement to seal conduit entrances, but more guidance is needed to ensure effective seals because merely meeting a standard doesn\u2019t guarantee that a seal will protect valuable assets from water, gas, rodents, dirt, or fire. Many installers (inspectors too) are unaware of the shortcomings of duct putty and open-cell foams. They naturally gravitate to the easiest and lowest-cost product, believing the code is met.<\/p>\n<p>The solution is for performance-based specifications in system design and best practices. Specifiers and engineers should analyze situational risks and establish performance criteria for effective seal integrity. Sealants should be sourced from reputable manufacturers offering products developed, tested, and rated specifically for conduits. Duct seal selection should be an informed process based on the risk profile of the application and the well-tested technical specifications of the chemical or mechanical sealing product.<\/p>\n<h2>Have any questions?<\/h2>\n<p><button class=\"button button--primary\" data-micromodal-trigger=\"polywater-modal--email-us-form\">Email Us <\/button><\/p>\n<div class=\"modal micromodal-slide\" id=\"polywater-modal--email-us-form\" aria-hidden=\"true\"><div class=\"modal__overlay\" tabindex=\"-1\" data-micromodal-close><div class=\"modal__container\" role=\"dialog\" aria-modal=\"true\" aria-labelledby=\"polywater-modal--email-us-form-title\"><header class=\"modal__header\"><h2 id=\"polywater-modal--email-us-form-title\">Email Us Form<\/h2><button class=\"button--secondary modal__close\" aria-label=\"Close modal\" data-micromodal-close><\/button><\/header><div id=\"polywater-modal--email-us-form-content\"><!-- [if lte IE 8]>\r\n<script charset=\"utf-8\" type=\"text\/javascript\" src=\"\/\/js.hsforms.net\/forms\/v2-legacy.js\"><\/script>\r\n<![endif]-->\r\n<script charset=\"utf-8\" type=\"text\/javascript\" src=\"\/\/js.hsforms.net\/forms\/v2.js\"><\/script>\r\n<script>\r\nhbspt.forms.create({\r\n  region: \"na1\",\r\n  portalId: \"6060295\",\r\n  formId: \"7658eeb9-0cf9-469d-a7f1-0f033127bb9d\",\r\n  onFormReady: function (a) {\r\n    a.on('change', function(){\r\n      var zip = a.find('input[name=\"zip\"]');\r\n      if( zip ) {\r\n        if( zip.val() && zip.val().length > 4 ) {\r\n          var url = \"https:\/\/api.zippopotam.us\/us\/\" + zip.val();\r\n          var client = new XMLHttpRequest();\r\n          client.open(\"GET\", url, true);\r\n          client.onreadystatechange = function() {\r\n            if(client.readyState == 4) {\r\n              var resp = JSON.parse(client.responseText);\r\n              var city = resp.places[0]['place name'];\r\n              var state = resp.places[0]['state'];\r\n              a.find('input[name=\"city\"]').val(city);\r\n              a.find('input[name=\"state\"]').val(state);\r\n            };\r\n          };\r\n          client.send();\r\n        }\r\n      }\r\n    });\r\n  },\r\n});\r\n<\/script><\/div><\/div><\/div><\/div>","protected":false},"excerpt":{"rendered":"<p>What the Codes Say: The infographic linked here and also found below, illustrates the need for duct seals and lists&#8230;<\/p>\n","protected":false},"author":7,"featured_media":13106,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_relevanssi_hide_post":"","_relevanssi_hide_content":"","_relevanssi_pin_for_all":"","_relevanssi_pin_keywords":"","_relevanssi_unpin_keywords":"","_relevanssi_related_keywords":"","_relevanssi_related_include_ids":"","_relevanssi_related_exclude_ids":"","_relevanssi_related_no_append":"","_relevanssi_related_not_related":"","_relevanssi_related_posts":"","_relevanssi_noindex_reason":"","footnotes":""},"categories":[2997,3000,3022,3004,3009],"tags":[],"industry-type":[2981],"writer":[2712],"class_list":["post-17181","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-system-hardening","category-duct-sealing","category-conduit-sealing","category-content-type","category-research-paper","industry-type-electrical-infrastructure","writer-chris-jonnes"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.2 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance. - Polywater<\/title>\n<meta name=\"description\" content=\"Dive into the gap between code compliance and effective duct sealing. Learn why meeting standards may not be enough to protect against damage. Uncover the importance of performance-based specifications and informed seal selection. Email us with questions and safeguard your utility infrastructure proactively.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance. - Polywater\" \/>\n<meta property=\"og:description\" content=\"Dive into the gap between code compliance and effective duct sealing. Learn why meeting standards may not be enough to protect against damage. Uncover the importance of performance-based specifications and informed seal selection. Email us with questions and safeguard your utility infrastructure proactively.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/\" \/>\n<meta property=\"og:site_name\" content=\"Polywater\" \/>\n<meta property=\"article:published_time\" content=\"2022-08-27T00:12:16+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2025-05-20T17:24:08+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/FST-cart-pumped-into-duct-700p.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"700\" \/>\n\t<meta property=\"og:image:height\" content=\"394\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Rick Schmolke\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Rick Schmolke\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"7 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/\"},\"author\":{\"name\":\"Rick Schmolke\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#\\\/schema\\\/person\\\/a60fe81e63d35625d9be04310f1601f4\"},\"headline\":\"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance.\",\"datePublished\":\"2022-08-27T00:12:16+00:00\",\"dateModified\":\"2025-05-20T17:24:08+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/\"},\"wordCount\":1259,\"image\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2021\\\/11\\\/FST-cart-pumped-into-duct-700p.jpg\",\"articleSection\":[\"System Hardening\",\"Duct Sealing\",\"Conduit Sealing\",\"Content Type\",\"Research Paper\"],\"inLanguage\":\"en-US\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/\",\"url\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/\",\"name\":\"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance. - Polywater\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2021\\\/11\\\/FST-cart-pumped-into-duct-700p.jpg\",\"datePublished\":\"2022-08-27T00:12:16+00:00\",\"dateModified\":\"2025-05-20T17:24:08+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#\\\/schema\\\/person\\\/a60fe81e63d35625d9be04310f1601f4\"},\"description\":\"Dive into the gap between code compliance and effective duct sealing. Learn why meeting standards may not be enough to protect against damage. Uncover the importance of performance-based specifications and informed seal selection. Email us with questions and safeguard your utility infrastructure proactively.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2021\\\/11\\\/FST-cart-pumped-into-duct-700p.jpg\",\"contentUrl\":\"https:\\\/\\\/www.polywater.com\\\/wp-content\\\/uploads\\\/2021\\\/11\\\/FST-cart-pumped-into-duct-700p.jpg\",\"width\":700,\"height\":394,\"caption\":\"FST cartridge pumped with a dispensing gun into a duct in a concrete wall. Some black wires protrude from the duct.\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance.\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#website\",\"url\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/\",\"name\":\"Polywater\",\"description\":\"Solutions at work.\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/#\\\/schema\\\/person\\\/a60fe81e63d35625d9be04310f1601f4\",\"name\":\"Rick Schmolke\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g\",\"caption\":\"Rick Schmolke\"},\"url\":\"https:\\\/\\\/www.polywater.com\\\/en\\\/knowledge-hub\\\/author\\\/rick\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance. - Polywater","description":"Dive into the gap between code compliance and effective duct sealing. Learn why meeting standards may not be enough to protect against damage. Uncover the importance of performance-based specifications and informed seal selection. Email us with questions and safeguard your utility infrastructure proactively.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/","og_locale":"en_US","og_type":"article","og_title":"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance. - Polywater","og_description":"Dive into the gap between code compliance and effective duct sealing. Learn why meeting standards may not be enough to protect against damage. Uncover the importance of performance-based specifications and informed seal selection. Email us with questions and safeguard your utility infrastructure proactively.","og_url":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/","og_site_name":"Polywater","article_published_time":"2022-08-27T00:12:16+00:00","article_modified_time":"2025-05-20T17:24:08+00:00","og_image":[{"width":700,"height":394,"url":"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/FST-cart-pumped-into-duct-700p.jpg","type":"image\/jpeg"}],"author":"Rick Schmolke","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Rick Schmolke","Est. reading time":"7 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#article","isPartOf":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/"},"author":{"name":"Rick Schmolke","@id":"https:\/\/www.polywater.com\/en\/#\/schema\/person\/a60fe81e63d35625d9be04310f1601f4"},"headline":"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance.","datePublished":"2022-08-27T00:12:16+00:00","dateModified":"2025-05-20T17:24:08+00:00","mainEntityOfPage":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/"},"wordCount":1259,"image":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#primaryimage"},"thumbnailUrl":"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/FST-cart-pumped-into-duct-700p.jpg","articleSection":["System Hardening","Duct Sealing","Conduit Sealing","Content Type","Research Paper"],"inLanguage":"en-US"},{"@type":"WebPage","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/","url":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/","name":"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance. - Polywater","isPartOf":{"@id":"https:\/\/www.polywater.com\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#primaryimage"},"image":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#primaryimage"},"thumbnailUrl":"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/FST-cart-pumped-into-duct-700p.jpg","datePublished":"2022-08-27T00:12:16+00:00","dateModified":"2025-05-20T17:24:08+00:00","author":{"@id":"https:\/\/www.polywater.com\/en\/#\/schema\/person\/a60fe81e63d35625d9be04310f1601f4"},"description":"Dive into the gap between code compliance and effective duct sealing. Learn why meeting standards may not be enough to protect against damage. Uncover the importance of performance-based specifications and informed seal selection. Email us with questions and safeguard your utility infrastructure proactively.","breadcrumb":{"@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#primaryimage","url":"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/FST-cart-pumped-into-duct-700p.jpg","contentUrl":"https:\/\/www.polywater.com\/wp-content\/uploads\/2021\/11\/FST-cart-pumped-into-duct-700p.jpg","width":700,"height":394,"caption":"FST cartridge pumped with a dispensing gun into a duct in a concrete wall. Some black wires protrude from the duct."},{"@type":"BreadcrumbList","@id":"https:\/\/www.polywater.com\/en\/knowledge-hub\/is-meeting-a-standard-enough-an-examination-of-duct-sealing-code-compliance\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.polywater.com\/en\/"},{"@type":"ListItem","position":2,"name":"Is Meeting a Standard Enough?\u2014An Examination of Duct Sealing Code Compliance."}]},{"@type":"WebSite","@id":"https:\/\/www.polywater.com\/en\/#website","url":"https:\/\/www.polywater.com\/en\/","name":"Polywater","description":"Solutions at work.","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.polywater.com\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/www.polywater.com\/en\/#\/schema\/person\/a60fe81e63d35625d9be04310f1601f4","name":"Rick Schmolke","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/53c2625a8c8a729cfdb238a18af45351278a1de8d575eb0c32622108d1a17c2b?s=96&d=mm&r=g","caption":"Rick Schmolke"},"url":"https:\/\/www.polywater.com\/en\/knowledge-hub\/author\/rick\/"}]}},"_links":{"self":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/posts\/17181","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/users\/7"}],"replies":[{"embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/comments?post=17181"}],"version-history":[{"count":0,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/posts\/17181\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/media\/13106"}],"wp:attachment":[{"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/media?parent=17181"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/categories?post=17181"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/tags?post=17181"},{"taxonomy":"industry-type","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/industry-type?post=17181"},{"taxonomy":"writer","embeddable":true,"href":"https:\/\/www.polywater.com\/en\/wp-json\/wp\/v2\/writer?post=17181"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}